Buried firefighting device, allowing connection at ground level of firefighting services mobile devices. It is fitted with a disconnectable flow-limiting system and a SECURE device to prevent street-pooling.
Applications :
- Public and private pressurized fire protection networks
Product benefits :
- Keyser fitting with declutchable flow-limiting system
- Built-in SECURE device
- Low operating torque
- Box reclining by 5° in all directions or adjustable in height by more than 30 mm
- Valve guide anti-water hammer and antivibration for progressive opening and closing, limiting water hammer
- Thick valve gasket, greater tightness with foreign bodies
- Duck foot with rotating flanges for a 360° rotation and easy positioning of the hydrant.
- Tilting lid, secured to the box, allowing a complete clearance of the outlet and operating square, effortless.
Range :
Technical data :
- Keyser outlet according to NF S 61-708 (with ministerial approval)
- Flange drilled to ISO PN 10/16 (EN 1092-2 andISO 7005-2 standards)
- No frost version with fixed hydraulic ball drain
- Connection depth 1 m.
- Black color lid as a standard according to NF EN 124 class 250
- Normalized operating square
- Clockwise closing (FSH)
- Anticorrosion protection epoxy coating applied by cataphoresis
- Complete tightness according to NF EN 12266-1 class A
Norms and certifications :
- Complies with NF EN 14339 standard
- Complies with NF EN 1074-6 standard
- Complies with NF EN 14339/CN standard (with ministerial approval)
- CE marking in accordance with EU regulations n°305/2011
- ACS (Attestation de Conformité Sanitaire)
- Production 100% tested according to NF EN 12266-1 standard
Alternatives and options :
- "Lutèce" version with connection to the safe box with a PE pipe DN 40 to channel water remaining in the safe box
- Version with removable hydraulic ball drain
- Red or yellow lid
Download Declaration of performance